Construction Charts

Concrete Air Content Chart: ACI Targets & Tolerances

ACI 318-19 Reference

Total air content targets by aggregate size and freeze-thaw exposure class, with field tolerances, ASTM test-method selection, and worked result interpretation.

F1 and F2/F3 targets±1.5 point toleranceASTM C231, C173, C138Worked examples📅 Last Updated: November 2026

⭐ Concrete Air Content Chart: Quick Reference

A concrete air content chart gives ACI 318-19 total air targets by nominal maximum aggregate size and freeze-thaw exposure class: for 3/4 in. aggregate, 5.0% for F1 and 6.0% for F2 and F3, each with a ±1.5 percentage-point field tolerance. These are code table values, not a universal air percentage.

ACI Air Content Targets by Aggregate Size

Concrete Air Content Chart by Aggregate Size and Freeze-Thaw Exposure (ACI 318-19 target total air, %)
Nominal maximum aggregate sizeApprox. metric sizeF1 target air (%)F2/F3 target air (%)
3/8 in.9.5 mm6.07.5
1/2 in.12.5 mm5.57.0
3/4 in.19 mm5.06.0
1 in.25 mm4.56.0
1-1/2 in.37.5 mm4.55.5
2 in.50 mm4.05.0
3 in.75 mm3.54.5

Source: ACI 318-19 Table 19.3.3.1 as reproduced in the ACI Foundation CRC 117 report (Table 2, ACI 318-19 columns) and the NRMCA guide to selecting exposure classes. Air content is total air by volume of freshly mixed concrete, including entrained and entrapped air.

✓ Checked against the ACI Foundation CRC 117 table and the NRMCA exposure-class guide (ACI 318-19 columns), November 2026
  • Values are total air content by volume of fresh concrete, including entrained and entrapped air.
  • F1, F2, and F3 are ACI freeze-thaw exposure classes, not general severity labels. The chart does not apply to concrete outside those requirements, and it is not a shotcrete table.
  • ACI 318-19 allows a field tolerance of ±1.5 percentage points. A 6.0% target means 4.5% to 7.5%, not 6.0% ± 1.5% of 6.0.
  • ACI 318-19 allows the specified air content to be reduced by 1 percentage point when the specified strength is 5000 psi or more (see Section 7).
  • Nominal maximum aggregate size comes from the approved mixture, not from looking at the stones. Verify the adopted code edition and project documents before using these values as acceptance criteria.

F1 vs. F2/F3 Exposure Classes

F1 is limited exposure to water; F2 and F3 are frequent exposure to water, and F3 adds deicing chemicals (see Section 5).

How to Read the Chart

Find the nominal maximum aggregate size, then read the column for the assigned exposure class. For complete size definitions see the nominal aggregate size chart.

1

3/4 in. aggregate: F1 vs. F2/F3

Given: Nominal maximum aggregate size 3/4 in. (19 mm)
1
Find 3/4 in. in the first column.
2
F1 target: 5.0% total air. F2 or F3 target: 6.0% total air.
Result: 5.0% for F1; 6.0% for F2/F3

Applies where the adopted code and project documents use ACI 318-19 and the exposure class is correctly assigned.

What Is Air Content in Concrete?

Air content is the percentage of the freshly mixed concrete volume occupied by air, so 6% air means 0.06 of the volume, or 1.62 ft³ in each cubic yard.

Total Air Content by Volume

A = (V_air ÷ V_concrete) × 100. It is a volumetric proportion, not an admixture dosage, and it is different from water content, porosity, and slump.

Air in Fresh Concrete

Fresh-concrete air is measured by ASTM test methods (see Section 15).

Why Air Content Matters

Concrete exposed to freezing and thawing needs an adequate air-void system; too much air can reduce strength and complicate finishing.

Air-Entrained vs. Non-Air-Entrained Concrete

Air-entrained concrete contains many small, intentionally stabilized bubbles, while non-air-entrained concrete still contains a smaller amount of larger entrapped air.

Entrained air vs. entrapped air
PropertyEntrained airEntrapped air
OriginIntentionally formed with an air-entraining admixtureIncidental, from mixing and handling
SizeSmall bubbles, stabilized in the pasteLarger, irregular voids
DistributionMany, closely spaced voidsFew, widely spaced voids
Freeze-thaw roleProvides pressure-relief spaceNot a reliable protection system
Present in non-air-entrained concrete?NoYes: measurable air can still be present

Concepts per the NRMCA CIP 2, Scaling Concrete Surfaces and the ACI Foundation CRC 117 report. Total air percentage alone does not describe the hardened air-void system.

Why Bubble Distribution Matters

Bubble size and spacing matter as much as the total percentage. See Section 24.

⭐ ACI 318 Concrete Air Content Requirements

ACI 318-19 Table 19.3.3.1 requires air-entrained concrete for exposure classes F1, F2, and F3, with a target total air content by aggregate size and a field tolerance of ±1.5 percentage points.

ACI 318-19 Table 19.3.3.1

The target values are in the main chart. ACI 201.2R-16 gives higher recommended values; do not mix its column with ACI 318-19 values.

ACI 201.2R-16 recommendations vs. ACI 318-19 targets (total air, %)
Nominal maximum aggregate sizeACI 201.2R-16 F1ACI 318-19 F1ACI 201.2R-16 F2/F3ACI 318-19 F2/F3
3/8 in.7.06.07.57.5
1/2 in.7.05.57.07.0
3/4 in.6.55.07.06.0
1 in.6.54.56.56.0
1-1/2 in.6.04.56.55.5
2 in.6.04.06.05.0
3 in.5.03.55.54.5

Source: ACI Foundation CRC 117 report, Table 2. Use the ACI 318-19 columns for the chart on this page; ACI 201.2R-16 is a guide with higher values. Both documents allow a field tolerance of ±1.5%.

✓ Checked against the ACI Foundation CRC 117 table and the NRMCA exposure-class guide (ACI 318-19 columns), November 2026

Field Tolerances

±1.5 percentage points on the target, subject to the project specification.

Adopted Code vs. Published Edition

The legally applicable code is the edition the jurisdiction adopts, and the project documents control. ACI 318-25 is the newest ACI edition (see the ACI 318 building code portal), so confirm whether the adopted edition and its table match these ACI 318-19 values before using them. Do not assume a newer edition has identical values.

⭐ Concrete Freeze-Thaw Exposure Classes F0 to F3

ACI 318-19 assigns F0 to F3 by freeze-thaw exposure, how frequently the concrete is exposed to water, and deicing chemicals, not by state climate or the word outdoor.

ACI 318-19 freeze-thaw exposure classes
ClassACI conditionExamples from ACI commentary (as summarized by NRMCA)Air-content implication
F0Concrete not exposed to freezing-and-thawing cyclesMembers the designer determines are not exposed to freezing and thawingNo F-class air target in the chart
F1Freezing and thawing with limited exposure to waterExterior walls, beams, girders, and slabs not in direct contact with soil, not subject to snow and ice accumulationUse the F1 target
F2Freezing and thawing with frequent exposure to waterExterior elevated slabs with snow and ice accumulation; members in contact with soilUse the F2/F3 target
F3F2 conditions plus exposure to deicing chemicalsHorizontal members in parking structures; foundation or basement walls extending above grade where deicing chemicals accumulateUse the F2/F3 target (plus other F3 limits)

Source: ACI 318-19 Table 19.3.1.1 and commentary as reproduced in the NRMCA guide to selecting exposure classes and NRMCA Guide to Improving Specifications for Ready Mixed Concrete. A simplified aid, not a substitute for the adopted ACI definitions. ACI commentary says to choose the more conservative F2 if there is doubt between F1 and F2. F0 does not mean zero air; it means no freeze-thaw air requirement.

✓ Class wording checked against the NRMCA guide quoting ACI 318-19, November 2026

F0, F1, F2, and F3

F1 and F2 do not anticipate deicing chemicals; F3 does. Assign the class by the exposure of each member rather than by climate alone.

⭐ Concrete Air Content by Aggregate Size

Smaller nominal maximum aggregate needs more total air, for example 6.0% (F1) and 7.5% (F2/F3) at 3/8 in. versus 3.5% and 4.5% at 3 in., because smaller aggregate means more paste and mortar.

3/8-Inch and 1/2-Inch Aggregate

6.0% and 7.5% at 3/8 in.; 5.5% and 7.0% at 1/2 in.

3/4-Inch and 1-Inch Aggregate

5.0% and 6.0% at 3/4 in.; 4.5% and 6.0% at 1 in.

1-1/2-Inch Through 3-Inch Aggregate

4.5% and 5.5% at 1-1/2 in.; 4.0% and 5.0% at 2 in.; 3.5% and 4.5% at 3 in.

Why Aggregate Size Changes the Target

Entrained air lives in the paste, so concrete with more paste per unit volume needs a higher total air content to keep a similar air fraction in the paste. ACI 201.2R-16 builds its values on 18% air in the paste fraction (ACI Foundation CRC 117 report). See the nominal aggregate size chart.

⭐ Concrete Air Content Tolerance Chart

ACI 318-19 allows ±1.5 percentage points on the target, so a 6.0% target gives a calculated interval of 4.5% to 7.5%, and a 5.0% target gives 3.5% to 6.5%.

Air content target and tolerance ranges (±1.5 percentage points)
Nominal maximum aggregate sizeF1 targetF1 calculated rangeF2/F3 targetF2/F3 calculated range
3/8 in.6.0%4.5 to 7.5%7.5%6.0 to 9.0%
1/2 in.5.5%4.0 to 7.0%7.0%5.5 to 8.5%
3/4 in.5.0%3.5 to 6.5%6.0%4.5 to 7.5%
1 in.4.5%3.0 to 6.0%6.0%4.5 to 7.5%
1-1/2 in.4.5%3.0 to 6.0%5.5%4.0 to 7.0%
2 in.4.0%2.5 to 5.5%5.0%3.5 to 6.5%
3 in.3.5%2.0 to 5.0%4.5%3.0 to 6.0%

Arithmetic on the ACI 318-19 targets with the ±1.5 percentage-point tolerance. ASTM C94 also uses ±1.5% for air content and has its own provisions for jobsite adjustment and retesting before rejection (NRMCA Guide to Improving Specifications for Ready Mixed Concrete). These are calculated intervals, not project acceptance specifications.

✓ Calculated from stated values, arithmetic checked, November 2026

What ±1.5 Percentage Points Means

It is an absolute difference in air percentage, not 1.5% of the target value.

1

Air content acceptance interval

Given: Target 6.0%; tolerance ±1.5 percentage points
1
A_min = 6.0 – 1.5 = 4.5%
2
A_max = 6.0 + 1.5 = 7.5%
Result: Calculated interval 4.5% to 7.5%

Use the tolerance prescribed by the governing project documents.

Lower and Upper Acceptance Limits

The table lists them by aggregate size and class. ACI 318-19 also allows the specified air content to be reduced by 1 percentage point when the specified compressive strength is 5000 psi or more (NRMCA guide to selecting exposure classes).

2

Strength-based reduction (ACI 318-19 provision)

Given: 3/4 in. aggregate, F2/F3 target 6.0%, specified f’c 5000 psi
1
Reduction allowed: 6.0 – 1.0 = 5.0%.
2
Range with ±1.5: 5.0 – 1.5 = 3.5% to 5.0 + 1.5 = 6.5%.
Result: Target 5.0%; range 3.5% to 6.5%

Applies only where the specification adopts that provision and f’c is at least 5000 psi. Confirm with the engineer of record.

How to Interpret Borderline Results

A reading at a boundary is within the calculated interval, but the project’s acceptance procedure decides what happens next.

Concrete Air Content for Driveways and Sidewalks

Driveways and sidewalks in freezing climates generally need air-entrained concrete, but not every U.S. driveway requires 6% air, because the target depends on exposure and aggregate size.

NRMCA rules for scaling-resistant exterior slabs
ItemRecommendation (NRMCA CIP 2)
Strength4000 psi for continuously moist slabs with deicers; 3500 psi otherwise
AirAir-entrained, about 6% for 3/4 in. or 1 in. aggregate
SlumpAbout 3 to 5 in.; do not add excess water
FinishingWait until bleed water is gone; avoid steel trowels and overworking
CuringCure properly; consider a breathable sealer
DeicersAvoid in the first winter; use moderate amounts afterward

Source: NRMCA CIP 2, Scaling Concrete Surfaces. Practical guidance, not a code requirement. See the proper concrete finishing practices guide for finishing steps.

✓ Confirmed in the NRMCA CIP 2 text, November 2026

Freeze-Thaw and Deicing Salt Exposure

The more often the slab is saturated and salted, the greater the scaling risk.

Surface Scaling Risk and Finishing

Finishing can reduce air near the surface. See the proper concrete finishing practices.

Concrete Air Content for Slabs and Floors

Exposed exterior slabs follow the freeze-thaw air targets, while protected interior floors have no ACI freeze-thaw air requirement, and no universal air maximum applies to every interior floor.

Exterior Slabs

Use the exposure class and aggregate size from the chart.

Interior Slabs

Interior concrete not exposed to freezing and thawing is F0, so the air chart does not apply.

Hard-Troweled Floors and Surface Defects

Entrained air can complicate dense, hard-troweled finishes, because finishing can trap air and water under the surface. Follow the project specification and the finishing guidance in the proper concrete finishing practices.

Air Content for Foundations, Walls and Structural Concrete

Whether a footing, wall, or column needs freeze-thaw air depends on its exposure to freezing, water, and deicing chemicals, not on what the member is called.

Exposure conditions, not member names, decide the need for freeze-thaw air
Member and conditionLikely class (ACI commentary examples)
Exterior wall, beam, or slab not in contact with soil, no snow or ice buildupF1
Exterior elevated slab with snow and ice accumulationF2
Horizontal and vertical members in contact with soil subject to freezingF2
Foundation or basement wall extending above grade, snow and ice buildupF2
Same wall where deicing chemicals accumulateF3
Member not exposed to freezing and thawing cyclesF0

Source: ACI 318-19 commentary examples as reproduced by the NRMCA guide to selecting exposure classes. The licensed design professional assigns the class; choose F2 if unsure between F1 and F2.

✓ Checked against the NRMCA guide quoting ACI commentary, November 2026

Below-Grade Concrete and Exposed Foundation Walls

Concrete the designer determines is not exposed to freezing and thawing is F0; walls extending above grade can be F2 or F3.

Structural Members Subject to Freezing

Check the exposure of each member and follow the engineer’s classification.

How Air Entrainment Improves Freeze-Thaw Durability

Entrained air gives freezing water in the cement paste nearby empty voids to expand into, which reduces internal pressure, and the spacing of those voids matters as much as total air.

Freezing Water in Cement Paste

Saturated paste develops internal stress as water freezes and expands. (NRMCA CIP 2, Scaling Concrete Surfaces)

Pressure Relief Through Air Voids

Millions of small air bubbles accommodate expanding water and ice and prevent stress buildup.

How entrained air protects concrete during freezingConceptual schematic, not a micrograph. Left: small separated air voids spread through cement paste, with short arrows from capillary pore water to nearby voids. Right: few widely separated voids, longer arrows, and a schematic microcracking indicator. No bubble sizes or spacing thresholds are implied.Distributed entrained air voidsWidely spaced voidsmicrocracking riskShorter pressure-relief distanceLonger pressure-relief distanceEntrained air voidCapillary pore waterWater moves toward a void during freezingConceptual schematic, not a micrograph. No bubble diameters or spacing-factor thresholds are implied.Total air percentage alone does not prove an adequate hardened air-void system.
Distributed entrained air voids shorten the distance water travels to a void; widely spaced voids lengthen it. Conceptual schematic.

Air-Void Spacing and Limits of Total Air Percentage

Total air does not describe the whole system. Research shows the spacing factor is a strong predictor of freeze-thaw durability (ACI Foundation CRC 117 report).

How Air Content Affects Concrete Strength

More air than the exposure requires can reduce compressive strength, but no universal psi loss per percentage point applies, because the effect depends on the mixture and its water-cementitious ratio.

Strength vs. Air Content

Entrained air is needed for durability, and raising air changes the achievable strength of a given mixture. ACI 318-19 recognizes this by allowing a 1 percentage point lower target at 5000 psi and above.

Mixture Proportioning

Compensate through proportioning, not by guessing a loss. See the concrete mix design reference and concrete mix ratio chart.

No Universal PSI-Loss Formula

Use the Concrete PSI Strength Calculator and the concrete strength gain chart for strength questions.

How Air Content Affects Workability and Finishing

Entrained air can improve cohesion and reduce bleeding, but air content is not slump, and inappropriate finishing can strip air from the surface.

Fresh Concrete Cohesion and Bleeding

Entrained air generally makes fresh concrete more cohesive and less prone to bleeding.

Finishing Response and Surface Durability

Do not finish with bleed water present, avoid overworking, and avoid steel trowels on exterior surfaces (NRMCA CIP 2, Scaling Concrete Surfaces).

Slump and air are separate measurements. See the concrete slump chart.

⭐ ASTM Concrete Air Content Testing Methods

Fresh-concrete air is measured by the pressure method (ASTM C231), volumetric method (ASTM C173), or gravimetric method (ASTM C138), and ASTM C457 evaluates the hardened air-void system.

ASTM concrete air content testing methods
MethodStandardMaterial testedMain purposeImportant limitation
PressureASTM C231/C231MFresh concreteAir from volume change under a known pressureNot suitable for lightweight or highly porous aggregates; needs the aggregate correction factor
VolumetricASTM C173/C173MFresh concreteAir removed by agitation in a water-filled vessel and read as a drop in water levelNeeds correct rolling, foam control, and reading
GravimetricASTM C138/C138MFresh concreteAir calculated from measured density and theoretical air-free densityNeeds accurate mixture and density data
MicroscopyASTM C457/C457MHardened concreteEvaluates air-void system parametersNot a routine fresh-concrete field test

Sources: ACI technical FAQ on fresh concrete air content; ASTM C231/C231M-26; ASTM C173/C173M-26; ASTM C457/C457M-24 (editions as listed in the approved outline, so confirm the edition your specification cites). The complete ASTM procedures govern actual testing.

✓ Method descriptions checked against the ACI technical FAQ, November 2026

ASTM C231, C173, C138, and C457

The pressure and volumetric methods have some advantage over the gravimetric method. For concrete made with low-density aggregates the pressure method cannot be used because of air in the aggregate pores, so the volumetric method is used (ACI technical FAQ on fresh concrete air content).

How to Test Concrete Air Content With a Pressure Meter

The pressure method (ASTM C231) finds air from the change in concrete volume under a known pressure and suits concrete made with relatively dense aggregates, using the aggregate correction factor.

When the Pressure Method Is Appropriate

Use it with dense aggregates. Do not use it with lightweight or highly porous aggregates.

Sampling and Preparing the Test

Use a representative sample and consolidate the meter bowl as the standard requires.

Aggregate Correction Factor

The factor corrects for air in the aggregate and must be determined for the aggregate in the mixture.

Reading and Recording the Result

Record the corrected reading with the sampling location. This is an overview, not a replacement for ASTM C231/C231M-26. Calibration, consolidation, and technician qualification matter.

Technician measuring fresh concrete air content using a pressure-type air meter
The ASTM C231 pressure method measures air content in fresh concrete containing suitable dense aggregates.

How to Test Concrete Air Content With a Volumetric Meter

The volumetric method (ASTM C173) removes air by agitating the concrete in a closed water-filled vessel and reads the drop in water level, so it suits lightweight and porous aggregates.

When to Use a Roll-A-Meter

Use it where aggregate pores would make a pressure reading unreliable.

General Measurement Principle

Air is displaced from the concrete and measured as a change in water level. Foam control and correct rolling are essential.

Common Testing Errors

Incorrect rolling, foam on the water, and misreading the neck are common errors. Follow ASTM C173/C173M-26 for the full procedure.

Volumetric air meter used to measure the air content of freshly mixed concrete
The ASTM C173 volumetric method is suitable for fresh concrete containing lightweight or highly porous aggregates.

⭐ How to Calculate Concrete Air Content

Air content is A = V_air ÷ V_concrete × 100, so 6% of a 27 ft³ cubic yard is 1.62 ft³, and the gravimetric method uses A = (T – D) ÷ T × 100.

Air Percentage From Volume

1

Air volume in one cubic yard

Given: A = 6%; 1 yd³ = 27 ft³
1
V_air = 27 × 6 ÷ 100
Result: V_air = 1.62 ft³

A volume illustration, not a way to add air. Air entrainment requires controlled proportioning and admixtures.

Gravimetric Air Content

3

Gravimetric air content (illustrative)

Given: T = 150 lb/ft³ (theoretical air-free density), D = 141 lb/ft³ (measured)
1
A = (T – D) ÷ T × 100
2
(150 – 141) ÷ 150 × 100 = 6.0%
Result: A = 6.0%

Illustration only. T must come from valid mixture-proportion data; do not assume 150 lb/ft³. Follow ASTM C138 for actual testing.

Target vs. Measured Air Content

2

Measured vs. target air

Given: Target 6.0%; measured 4.8%
1
ΔA = 4.8 – 6.0
Result: ΔA = -1.2 percentage points

Inside a ±1.5 point interval, if that tolerance applies.

4

Percentage points vs. relative change

Given: Air changes from 6% to 5%
1
Percentage points: 5 – 6 = -1 percentage point
2
Relative: (5 – 6) ÷ 6 × 100 = -16.67%
Result: -1 point, or a 16.67% relative decrease

Use percentage points for tolerances and field-reading differences.

⭐ Concrete Air Content Field Test Examples

With a 6.0% target and ±1.5 point tolerance, a 4.0% reading is below the 4.5% to 7.5% range, while 7.0% is within it, and the project procedure decides what follows.

Field air test interpretation, 3/4 in. aggregate, F2/F3 target 6.0%, tolerance ±1.5 points
Measured air (%)Difference from targetArithmetic comparison
4.0-2.0 pointsBelow calculated range
4.5-1.5 pointsAt lower boundary
5.5-0.5 pointsWithin calculated range
6.00.0 pointsExactly at target
7.0+1.0 pointWithin calculated range
7.5+1.5 pointsAt upper boundary
8.0+2.0 pointsAbove calculated range

Interprets numbers only; it does not authorize acceptance or rejection. The project test and acceptance provisions govern.

✓ Calculated from stated values, arithmetic checked, November 2026

Result Within, Below, or Above Tolerance

5.5% and 7.0% are within; 4.0% is below; 8.0% is above.

Borderline and Retest Situations

Readings at 4.5% and 7.5% sit on the boundary. Retesting follows the specification and the applicable ASTM sampling and test rules.

What Causes Low Air Content in Concrete?

Low air content can come from admixture dosage or compatibility, mixing and transport, pumping and consolidation, temperature and mixture changes, or a sampling and testing problem, and no single factor always explains it.

Admixture Dosage and Compatibility

Dosage errors and interactions with other admixtures or materials can reduce entrained air.

Mixing and Transport

Mixing time, speed, and haul time affect air.

Pumping and Consolidation

Pumping and overworking can reduce air.

Temperature and Mixture Changes

Changes in materials, mixture, or temperature can shift air.

Sampling or Testing Problems

A wrong method, uncalibrated meter, or poor consolidation of the sample gives a false reading.

What Causes Excessive Air Content in Concrete?

Excessive air can result from air-entraining admixture dosage, chemical interactions, mixing conditions, material variability, or measurement and calibration errors, and unapproved jobsite adjustments should be avoided.

Air-Entraining Admixture Dosage and Chemical Interactions

Overdose or interactions with other admixtures can raise air.

Mixing Conditions and Material Variability

Mixer type, mixing time, and material changes affect air.

Measurement and Calibration Errors

Verify the test and calibration first, then consult the supplier and quality personnel. Do not make unapproved adjustments at the jobsite.

Air Content Changes During Pumping and Placement

Air content can change as concrete is handled, so before-pump and after-pump readings can differ, and the specified sampling location determines which reading applies; no fixed percentage loss from pumping exists.

Before-Pump and After-Pump Readings

Sample at the location named in the project specification.

Pressure, Bubble Stability, and Placement Effects

Pump pressure, line configuration, drops, and consolidation can all affect air.

Project-Specified Sampling Location

Confirm it before the pour so the reading is acceptable under the specification.

Air Content and Concrete Surface Scaling

Scaling is most often caused by non-air-entrained concrete or too little entrained air, especially at the surface, so proper air must be paired with good mixture quality, finishing, and curing.

Scaling and air content
TopicWhat the NRMCA guidance says
What scaling isLocal flaking or peeling of the finished surface from freezing and thawing
Main causesNon-air-entrained or too little air (especially at the surface), low strength, wrong mixture, excess deicers on new concrete, poor finishing, insufficient curing
Role of airMillions of small bubbles accommodate expanding water and ice
FinishingPlacing and finishing can reduce entrained air at the surface
Quality controlProper air is one part of durability alongside mixture quality, placement, curing, and exposure

Source: NRMCA CIP 2, Scaling Concrete Surfaces.

✓ Confirmed in the NRMCA CIP 2 text, November 2026

Freeze-Thaw Scaling and Deicing Chemicals

Deicers increase saturation at the surface and the number of freeze-thaw cycles.

Finishing-Related Air Loss and Prevention

See the proper concrete finishing practices for finishing sequence.

Air Content vs. Air-Void Spacing Factor

A fresh air reading does not prove an adequate hardened air-void system, because spacing factor and void size, measured on hardened concrete by ASTM C457, drive freeze-thaw durability.

Total air content vs. air-void spacing factor
PropertyWhat it measuresHow it is determined
Total air contentPercent of concrete volume that is airFresh-concrete tests such as ASTM C231, C173, C138
Air-void size distribution and specific surfaceHow fine the air voids areHardened-concrete microscopy (ASTM C457)
Spacing factorMean half-distance between entrained air voidsASTM C457, which requires a trained petrographer
Cost and timingSlower and more expensive than fresh testsOften used for pre- or post-qualification

Sources: ACI Foundation CRC 117 report (spacing factor critical since 1949 but not specified by ACI committees; total air does not guarantee a quality air-void system; spacing factors of about 0.009 in. (0.23 mm) are cited in ACI 201 commentary and reported to be reachable across a total air range of about 3% to 7%); ASTM C457/C457M-24. These are reference observations, not an acceptance criterion.

✓ Checked against the ACI Foundation CRC 117 report, November 2026

Hardened-concrete microscopy needs a trained petrographer and is not a routine fresh-concrete acceptance test.

⭐ What to Do When Concrete Air Content Is Out of Specification

When air content is out of specification, first verify the test and sample, check the approved mix and delivery ticket, notify the responsible parties, and follow the project acceptance procedure, without ad hoc jobsite changes.

Out-of-range air content troubleshooting
FindingPossible causes to investigateAppropriate next action
Low airDosage, admixture compatibility, air loss, testing errorVerify test, mixture, and delivery conditions
High airAdmixture dosage, mixing conditions, material changesVerify test and consult supplier or quality personnel
Pressure and volumetric readings disagreeMethod suitability, aggregate characteristics, procedureCheck method and aggregate type
Change after pumpingTransport and placement effectsFollow the specified sampling and testing protocol
Inconsistent repeated readingsSampling, equipment, operator, mixture variabilityReview calibration and sampling procedures
Passing fresh air but later scalingSurface finishing, curing, exposure, hardened void systemInvestigate the full durability history

A diagnostic framework only. ASTM C94 sets a ±1.5% tolerance, permits a jobsite adjustment when air is below the lower limit, and has retesting procedures before rejection (NRMCA Guide to Improving Specifications for Ready Mixed Concrete); the project acceptance procedure and specification control. No automatic addition of air-entraining admixture, water, or chemicals is recommended here.

Concrete air test acceptance decision flowSeven-step sequence followed by decision branches. Example: target 6.0 percent, assumed tolerance plus or minus 1.5 percentage points, calculated limits 4.5 to 7.5 percent, measured 4.0 percent, which is below the calculated lower limit. The diagram does not prescribe automatic acceptance, rejection, or chemical adjustment.1Identify the approved concrete mixture2Confirm exposure class and nominal maximum aggregate size3Read the specified air target and tolerance4Confirm sampling location and ASTM test method5Record the measured air content6Compare with the applicable limits7Follow the project acceptance or investigation procedureWithin specifiedlimits?Yes: record the result andproceed under project QCNo: verify test validity and notifyresponsible quality-control personnelWrong method or invalid sample?Repeat testing per the applicable procedureNumerical exampleTarget: 6.0%Assumed tolerance: ± 1.5 percentage pointsCalculated limits: 4.5% to 7.5%Example measured value: 4.0%Classification: below the calculated lower limitThis is arithmetic, not an acceptance decision.The diagram does not prescribe automatic acceptance, rejection, or chemical adjustment. The governing specification controls.Use the tolerance in the project documents, not an assumed value.
Air-content results are evaluated against the specified target, tolerance, test method, and sampling requirements.

Verify the Test and Sample

Check the method, calibration, and sampling location.

Check the Approved Mix and Delivery Ticket

Confirm the mixture and aggregate size match the approved submittal.

Notify and Document

Notify the responsible parties, follow the acceptance procedure, and document corrective action.

Common Concrete Air Content Mistakes

The most common air content mistakes are applying 6% everywhere, using the wrong test method, and reading a percentage-point tolerance as a percentage of the target.

Common air content mistakes and corrections
MistakeCorrection
Assuming all exterior concrete needs 6%Use the exposure class and aggregate size; 6% is the 3/4 in. F2/F3 value
Confusing entrained and entrapped airEntrained air is the stabilized small-bubble system; entrapped air is incidental
Using the wrong test methodUse the pressure method with dense aggregates and the volumetric method with lightweight or porous aggregates
Ignoring aggregate sizeRead the row for the nominal maximum size in the approved mix
Misreading percentage-point tolerances±1.5 points is absolute, not 1.5% of the target
Confusing fresh and hardened air contentA fresh reading does not verify the hardened air-void system

Concrete Air Content FAQs

These are the most common questions about concrete air content, answered with ACI 318-19 values and ASTM test methods.

What is the normal air content of concrete?

There is no single normal value. Concrete exposed to freezing and thawing is air-entrained, with ACI 318-19 targets from 3.5% to 7.5% depending on aggregate size and exposure class, while concrete not exposed to freezing has no freeze-thaw air target. Always use the project specification and aggregate size.

Is 5% air content acceptable?

It depends. For 3/4 in. aggregate, 5.0% is the ACI 318-19 F1 target and is within the 4.5% to 7.5% interval for a 6.0% F2/F3 target. For other aggregate sizes or classes it may be outside the range, so compare it with the specified target and tolerance.

Is 6% air content good for concrete?

Six percent is the ACI 318-19 F2/F3 target for 3/4 in. and 1 in. aggregate, and NRMCA recommends about 6% for exterior slabs with those aggregates. It is not right for every mix, because smaller aggregate needs more and larger aggregate needs less.

What is the air content for 3/4-inch aggregate?

Under ACI 318-19 Table 19.3.3.1, 3/4 in. nominal maximum aggregate has a 5.0% target for F1 and 6.0% for F2 and F3, with a field tolerance of ±1.5 percentage points. The adopted code and project specifications control the value used for acceptance.

What is the recommended air content for a concrete driveway?

For a driveway exposed to freezing, moisture, and deicers with 3/4 in. or 1 in. aggregate, the ACI 318-19 F2/F3 target and NRMCA guidance are both about 6%. A driveway not exposed to freezing needs no freeze-thaw air target, so the right value depends on the project specification.

Does concrete need air entrainment in warm climates?

ACI 318 requires air entrainment for concrete exposed to freezing and thawing (F1 to F3). Concrete that is not exposed to freezing, such as in a warm climate or a protected interior, is classified F0 and has no freeze-thaw air target, though a specification can still ask for air.

What is the difference between F1, F2, and F3?

F1 is freezing and thawing with limited exposure to water, F2 is frequent exposure to water, and F3 is frequent exposure to water plus deicing chemicals. F2 and F3 share the same air targets. If there is doubt between F1 and F2, ACI commentary says to choose F2.

What is the tolerance for concrete air content?

ACI 318-19 and ASTM C94 use ±1.5 percentage points on the target, so a 6.0% target gives 4.5% to 7.5%. The tolerance is absolute, not a percentage of the target, and the project specification can set a different range, so use the tolerance written in the contract documents.

Does air entrainment reduce concrete strength?

Adding air can reduce compressive strength for a given mixture, but the amount depends on the mixture and water-cementitious ratio, so no universal psi loss per percentage point applies. ACI 318-19 recognizes the trade-off by allowing the target to drop 1 point at 5000 psi and above.

Can concrete have too much air?

Yes. Air above the intended range can reduce strength and make finishing harder. Check the test and calibration first, then follow the project acceptance procedure with the supplier and quality personnel. Do not make unapproved jobsite adjustments to bring air down.

What happens if air content is too low?

Concrete exposed to freezing and thawing becomes more vulnerable to scaling and freeze-thaw damage, especially at the surface. Verify the test, mix, and delivery conditions, notify the responsible parties, and follow the acceptance procedure rather than assuming a field fix will restore protection.

Can a concrete pump reduce air content?

It can. Air content may change as concrete is pumped and placed, so before-pump and after-pump readings can differ. No fixed percentage loss applies to every pump or mix, so test at the sampling location named in the project specification and record where the sample was taken.

What is the difference between ASTM C231 and C173?

C231 is the pressure method, which finds air from the volume change under a known pressure and needs an aggregate correction factor. C173 is the volumetric method, which removes air by agitation in water and reads the water level, and it is used with lightweight or porous aggregates.

Can the pressure method be used with lightweight aggregate?

Generally no. Air held in the pores of low-density or highly porous aggregate makes the pressure method unreliable, so the volumetric method (ASTM C173) is used instead. Check the standard and the project specification for the aggregate in the approved mixture before choosing the test.

Does a passing fresh-air test guarantee freeze-thaw durability?

No. A fresh-air test measures total air, not the spacing and size of the hardened air voids. Transport, pumping, finishing, and curing also affect the final system, and ASTM C457 microscopy is the method that evaluates the hardened air-void system in a core.

Can air content be adjusted after the concrete arrives?

Only under the governing specification and ASTM C94 procedures, which set their own conditions and retesting rules. Do not add air-entraining admixture, water, or chemicals on your own. Verify the test first, notify the responsible parties, and follow the project acceptance process.

Is air-entrained concrete suitable for hard-troweled floors?

Often not. Dense, hard-troweled interior finishes can blister or delaminate when entrained air and bleed water are trapped under the surface. Interior floors not exposed to freezing have no ACI freeze-thaw air requirement, so follow the floor specification and finishing guidance.

How is hardened concrete air content tested?

ASTM C457 uses microscopy on hardened concrete to determine air-void system parameters such as spacing factor and specific surface. It needs a trained petrographer, takes time, and is not a routine fresh-concrete field test, so it is used for pre-qualification or investigation.

Using the Concrete Air Content Chart

This concrete air content chart gives ACI 318-19 target air by aggregate size and exposure class, with tolerances, test methods, and result interpretation.

Assign the exposure class, take the nominal maximum aggregate size from the approved mix, read the target and tolerance, and confirm the adopted code and project documents. Choose the ASTM method that suits the aggregate, treat the arithmetic as interpretation rather than acceptance, and remember that a fresh-air reading does not prove the hardened air-void system. For related references see the concrete slump chart, nominal aggregate size chart, and concrete mix design reference.

📄 Download Concrete Air Content Chart PDF

Use your browser print function to save this page as a print-ready PDF for the field and submittal folder. Buttons and image placeholders are hidden when printing.

  • ACI air content chart
  • Tolerance range table
  • Exposure class guide
  • ASTM method comparison
  • Worked examples

Cite or Embed This Chart

Copy the code below to cite the full chart on your site. Each section also has a copy-citation button, and each table has an embed button.

<p>Concrete Air Content Chart via <a href=”https://concretecalculate.com/concrete-air-content-chart/”>ConcreteCalculate.com</a></p>