Construction Charts

Copper Pipe Wall Thickness Chart: Type K, L & M

ASTM B88 and CDA Reference

A copper pipe wall thickness chart lists the nominal wall of ASTM B88 Type K, L and M tube by size. For 1/2 inch nominal tube, walls are 0.049 inch (K), 0.040 inch (L) and 0.028 inch (M), all with a 0.625 inch outside diameter.

Type K, L and M wallsInside diameter and weightInches and millimetersWorked calculationsLast updated: November 2026

Copper Pipe Wall Thickness Chart: Quick Reference

Type K, L and M Thicknesses

Nominal wall thickness for ASTM B88 copper water tube ranges from 0.025 inch for 3/8 inch Type M to 0.405 inch for 12 inch Type K, and it rises with both size and type. Highlighted rows are the two sizes most often looked up.

Copper Pipe Wall Thickness Chart: ASTM B88 Type K, L and M (nominal values, inches)
Nominal copper size (in.)Actual OD (in.)Type K wall (in.)Type L wall (in.)Type M wall (in.)
1/40.3750.0350.030N/L
3/80.5000.0490.0350.025
1/20.6250.0490.0400.028
5/80.7500.0490.042N/L
3/40.8750.0650.0450.032
11.1250.0650.0500.035
1-1/41.3750.0650.0550.042
1-1/21.6250.0720.0600.049
22.1250.0830.0700.058
2-1/22.6250.0950.0800.065
33.1250.1090.0900.072
3-1/23.6250.1200.1000.083
44.1250.1340.1100.095
55.1250.1600.1250.109
66.1250.1920.1400.122
88.1250.2710.2000.170
1010.1250.3380.2500.212
1212.1250.4050.2800.254

Source: Copper Development Association, CDA Copper Tube Handbook (A4015-24/23), Tables 14.2a, 14.2b and 14.2c. Values are nominal inch dimensions.

<p>Copper Pipe Wall Thickness Chart via <a href=”https://concretecalculate.com/copper-pipe-wall-thickness-chart/#quick-reference”>ConcreteCalculate.com</a></p>
  • Values are nominal wall thicknesses for the listed U.S. copper water-tube types.
  • N/L means the size and type combination is not listed in the CDA reference table. It does not mean zero.
  • The OD column applies to ASTM B88 water-tube sizing, not to all copper tubing.
  • Actual manufactured dimensions are subject to the applicable product tolerances.
  • Wall thickness alone does not establish allowable operating pressure or fitting compatibility.
  • This table is a dimensional reference, not permission to substitute one tube type for another.

How to Read the Chart

Find your nominal size in the first column, then read across to the type you have. The OD is the same for all three types at a given size, so only the wall changes. For the broader sizing system, fittings and tube identification, see our Copper Pipe Size Chart.

1/2-Inch and 3/4-Inch Examples

Nominal 1/2 inch tube has a 0.625 inch OD and a nominal wall of 0.049, 0.040 or 0.028 inch for Types K, L and M. Nominal 3/4 inch tube has a 0.875 inch OD with walls of 0.065, 0.045 and 0.032 inch, which gives the inside diameters below.

1
3/4-Inch Copper Water Tube: Wall and Inside Diameter
Given: nominal 3/4 inch ASTM B88 tube, OD = 0.875 in.
1
Formula: ID = OD − 2t
2
Type K: 0.875 − 2(0.065) = 0.745 in
3
Type L: 0.875 − 2(0.045) = 0.785 in
4
Type M: 0.875 − 2(0.032) = 0.811 in
Result: Type K 0.745 in, Type L 0.785 in, Type M 0.811 in (nominal ID).

What it means: All three tubes share the same 0.875 inch OD, but the thicker wall leaves a smaller bore. The nominal values agree with CDA’s Type L table.

What Is Copper Pipe Wall Thickness?

Copper pipe wall thickness is the radial distance between a tube’s outside and inside surfaces, for example 0.045 inch for nominal 3/4 inch Type L. It is one wall, not the OD minus the ID, because that difference equals two walls (2t).

Meaning of Wall Thickness

Wall thickness (t) is measured from the outer surface to the inner surface through the metal. Because the tube has a wall on both sides of the bore, the OD is larger than the ID by exactly 2t. For 3/4 inch Type L, 0.875 inch minus 0.785 inch is 0.090 inch, which is twice the 0.045 inch wall.

Outside Diameter vs. Inside Diameter

For Type K, L and M water tube, the OD stays fixed for a given nominal size and the ID changes with the wall. That is why a thick Type K tube and a thin Type M tube of the same size fit the same fittings but carry different bore areas. Our Pipe Outside Diameter Chart and Pipe Inside Diameter Chart cover these two dimensions across many pipe materials.

Nominal vs. Measured Dimensions

Chart values are nominal, meaning the target dimension in the product standard. A tube you measure with a micrometer will differ slightly because manufacturing tolerances apply. Treat a chart value as the specified target, not as a guaranteed reading on every piece.

ASTM B88 Copper Water Tube Standards

ASTM B88-22 is the inch-pound specification for seamless copper water tube, and it defines the Type K, L and M sizes and walls used in this chart. ASTM lists B88-22 as the active inch-pound edition, and the CDA handbook publishes the dimensions as calculated tables.

ASTM B88-22

ASTM B88 covers seamless copper water tube for general plumbing and related fluid-conveyance uses. All tube supplied to these ASTM standards is at least 99.9 percent copper, and the usual alloy is phosphorus-deoxidized copper (UNS C12200), according to the CDA Copper Tube Handbook (A4015-24/23).

ASTM B88M-26

ASTM B88M-26 is the metric companion standard, updated in October 2026. Do not label the inch-pound standard “B88-26” just because the metric edition carries a 2026 date.

Product Dimensions and Tolerances

Table 1 of the ASTM specification gives nominal dimensions and permitted variations by size and type. This page uses CDA’s published nominal values, so confirm the current edition and the tolerance table when you write a purchase specification.

Standards vs. Plumbing-Code Requirements

An ASTM standard defines the product. The adopted plumbing or mechanical code, the project specification and the authority having jurisdiction decide where each type may be used. CDA states directly that codes govern which types may be used for a given application.

Type K vs. Type L vs. Type M Copper Wall Thickness

For the same nominal size, Type K has the thickest wall, Type L is intermediate and Type M is thinnest, and all three share one OD. At 3/4 inch the walls are 0.065, 0.045 and 0.032 inch respectively.

Thickness Hierarchy

The order K, L, M holds for every size in the chart. The gap is not constant, though. Type K at 3/4 inch is 44.4 percent thicker than Type L, while at 1/2 inch it is 22.5 percent thicker.

Differences at the Same Nominal Size

Same-Size Wall Comparison at Two Common Sizes (nominal, inches)
Nominal sizeType K wallType L wallType M wallK thicker than LL thicker than M
1/20.0490.0400.02822.5%42.9%
3/40.0650.0450.03244.4%40.6%

Percent difference = (tA − tB) / tB x 100, calculated from CDA nominal walls (Tables 14.2a to 14.2c). This compares thickness only, not pressure rating or service life.

How Thickness Affects Inside Diameter

Because the OD is fixed, each extra 0.001 inch of wall removes 0.002 inch from the ID. At 3/4 inch, Type K leaves a 0.745 inch bore and Type M leaves 0.811 inch, a 0.066 inch difference.

Type K, L and M copper wall thickness at nominal 3/4 inch size Three cross-sections with the same 0.875 inch outside diameter. Type K wall 0.065 inch and inside diameter 0.745 inch. Type L wall 0.045 inch and inside diameter 0.785 inch. Type M wall 0.032 inch and inside diameter 0.811 inch. Nominal 3/4 inch copper water tube: same OD, different walls Wall t = 0.065 inType KOD 0.875 in (all three)Wall 0.065 inID 0.745 inWall t = 0.045 inType LOD 0.875 in (all three)Wall 0.045 inID 0.785 inWall t = 0.032 inType MOD 0.875 in (all three)Wall 0.032 inID 0.811 in Schematic cross-sections drawn to one common scale. Nominal dimensions per ASTM B88 as tabulated by CDA (Tables 14.2a to 14.2c). ID = OD minus 2t. Actual tube varies within ASTM tolerances.
Comparison of Type K, L and M copper water-tube wall thicknesses at the same nominal 3/4-inch size.

Why Thicker Is Not Automatically the Best Choice

A thicker wall adds cost, weight and a smaller bore. CDA’s application guidance notes that strength, formability and other mechanical factors drive the choice, and that codes control which types are allowed. For example, CDA recommends Types K or L where bending is required for fire sprinkler systems and Type M hard for straight runs, subject to the governing code.

Type K Copper Pipe Wall Thickness

Type K is the thickest standard copper water tube, with a nominal wall of 0.049 inch at 1/2 inch and 0.065 inch at 1 inch. It is green-marked on drawn tube and supplied in both drawn and annealed forms.

Type K Dimensional Characteristics

Nominal 1/2 inch Type K has a 0.625 inch OD, a 0.049 inch wall and a 0.527 inch ID. Nominal 1 inch Type K has a 1.125 inch OD, a 0.065 inch wall and a 0.995 inch ID, with a tube-only weight of about 0.839 lb/ft.

Typical Applications

CDA lists domestic water service and distribution, fire protection, solar, fuel oil, HVAC and snow melting among the applications for Type K. Whether Type K is required, allowed or preferred on a project depends on the approved specification and local requirements.

Drawn and Annealed Products

CDA states that Types K and L are made in drawn (hard) temper from 1/4 through 12 inch and in annealed (soft) coils from 1/4 through 2 inch. Temper changes how the tube is joined and how its pressure rating is evaluated.

Identification Markings

Type K carries a green color stripe on drawn tube, plus incised markings for tube type, manufacturer and country of origin. See the identification section below for how to confirm a type when markings are worn.

Type L Copper Pipe Wall Thickness

Type L is the intermediate copper water tube, with a nominal wall of 0.040 inch at 1/2 inch and 0.045 inch at 3/4 inch. It is blue-marked on drawn tube and widely used in both plumbing and mechanical systems.

Type L Dimensional Characteristics

Reference example: nominal 1/2 inch Type L has a 0.625 inch OD, a 0.040 inch wall, a 0.545 inch ID and a nominal bore area of 0.233 in². Its tube-only weight is about 0.285 lb/ft.

Plumbing and Mechanical Applications

CDA lists domestic water, fire protection, solar, fuel oil, natural gas, LP gas, HVAC and snow melting among Type L applications. CDA’s handbook also names Type L soft where coils are more convenient for underground water services and for radiant heating.

Comparison With Type K and M

At 1/2 inch, Type L is 0.009 inch thinner than Type K and 0.012 inch thicker than Type M. In percentage terms, K is 22.5 percent thicker than L, and L is 42.9 percent thicker than M.

Type M Copper Pipe Wall Thickness

Type M is the thinnest of the three water-tube types, with a nominal wall of 0.028 inch at 1/2 inch and 0.032 inch at 3/4 inch. It is red-marked and, according to CDA, supplied only in drawn (hard) temper.

Type M Dimensional Characteristics

Nominal 1/2 inch Type M has a 0.625 inch OD, a 0.028 inch wall, a 0.569 inch ID and about 0.204 lb/ft of copper. Type M is not listed in the 1/4 inch and 5/8 inch sizes in the CDA reference table.

Common Uses and Limitations

CDA lists domestic water service and distribution, fire protection, solar, fuel oil, HVAC and snow melting among Type M applications, and recommends Type M hard for many above-ground and below-ground distribution runs. The thin wall leaves less margin for mechanical damage, so use it where the design and code allow.

Product Availability and Code Acceptance

Type M is not prohibited everywhere and not allowed for every potable-water installation. Acceptance depends on the adopted plumbing code, the project specification and the application, such as buried service, so check them before ordering.

Copper Pipe Nominal Size vs. Actual Outside Diameter

For ASTM B88 Type K, L and M tube, the actual outside diameter is the nominal size plus 0.125 inch, so nominal 1/2 inch copper has a 0.625 inch OD. The same rule applies to DWV tube, but not to ACR tubing.

The 1/8-Inch OD Difference

Formula:

OD = N + 0.125 in.

Where N is the nominal tube size in inches. Example: N = 1/2 = 0.500 in., so OD = 0.500 + 0.125 = 0.625 in.

1/2-Inch Copper Pipe Example

Nominal Size to Actual OD (OD = N + 0.125 in.)
Nominal copper size (in.)Actual OD (in.)
1/20.625
3/40.875
11.125
22.125

Source: CDA Copper Tube Handbook (A4015-24/23), Section 1 and Tables 14.2a to 14.2d.

Why Nominal Size Is Not a Caliper Measurement

Nominal size is a trade name, not a reading you can take with calipers. A caliper on a 1/2 inch nominal tube reads about 0.625 inch, so a caliper never returns the nominal size. Our Copper Pipe Size Chart explains the full sizing system, and the Pipe Outside Diameter Chart compares OD across pipe materials.

Caliper reading 0.625 inch on the outside of nominal 1/2 inch copper water tube
A caliper reads 0.625 in. on nominal 1/2 inch copper tube, which is the actual OD, not the nominal size.

Copper Pipe Inside Diameter by Wall Thickness

Nominal inside diameter equals the OD minus twice the wall, so nominal 3/4 inch Type L has an ID of 0.875 − 2(0.045) = 0.785 inch. The ID drives bore area, water volume and friction loss, which is why it differs between K, L and M at the same size.

Calculating ID From OD

ID = OD − 2t

Use the OD for the nominal size from the main chart and the wall for the type you have. For 3/4 inch Type K, ID = 0.875 − 2(0.065) = 0.745 inch.

Copper tube cross-section: OD, wall thickness and inside diameter Nominal 1/2 inch Type L copper water tube. Actual outside diameter 0.625 inch, nominal wall thickness 0.040 inch on each side, inside diameter 0.545 inch. Inside diameter equals outside diameter minus two times wall thickness. Nominal 1/2 inch Type L copper tube: OD, wall and ID Centerline t = 0.040 in t = 0.040 in ID 0.545 in OD 0.625 in (full diameter) Tube data (nominal) Nominal size: 1/2 inch Actual OD: 0.625 in Wall t: 0.040 in (each side) Inside diameter: 0.545 in ID = OD − 2t 0.625 − 2(0.040) = 0.545 in t is one radial wall thickness. OD and ID are full diameters. Schematic, drawn to scale. ASTM B88 Type L, nominal values per CDA Table 14.2b.
Copper tube cross-section showing how nominal wall thickness determines inside diameter.

Type K/L/M Inside Diameter Comparison

Copper Inside Diameter by Tube Type (nominal, inches)
Nominal size (in.)OD (in.)Type K ID (in.)Type L ID (in.)Type M ID (in.)
1/20.6250.5270.5450.569
3/40.8750.7450.7850.811
11.1250.9951.0251.055
1-1/41.3751.2451.2651.291
1-1/21.6251.4811.5051.527
22.1251.9591.9852.009

Source: calculated from CDA nominal dimensions, Tables 14.2a to 14.2c. Values match CDA’s published inside diameters.

<p>Copper Inside Diameter by Tube Type via <a href=”https://concretecalculate.com/copper-pipe-wall-thickness-chart/#inside-diameter-by-wall-thickness”>ConcreteCalculate.com</a></p>

Why ID Matters for Hydraulic Calculations

Bore area and water velocity both depend on the ID. CDA advises keeping velocity at or below 8 ft/s for cold water and 5 ft/s for hot water up to about 140°F. For other materials and the full inside-diameter lookup, use the Pipe Inside Diameter Chart.

Copper Pipe Wall Thickness in Millimeters

To convert a copper wall thickness to millimeters, multiply inches by 25.4, so the 0.045 inch wall of 3/4 inch Type L equals 1.143 mm. These are exact conversions of the nominal inch values, not a reproduction of the separate ASTM B88M schedule.

Inch-to-Millimeter Conversion

t(mm) = 25.4 x t(in.)

Example: 0.045 in. x 25.4 = 1.143 mm, rounded to three decimals.

Common K/L/M Thicknesses in Metric

Copper Wall Thickness in Inches and Millimeters (nominal)
Nominal size (in.)K (in.)K (mm)L (in.)L (mm)M (in.)M (mm)
1/20.0491.2450.0401.0160.0280.711
3/40.0651.6510.0451.1430.0320.813
10.0651.6510.0501.2700.0350.889
1-1/40.0651.6510.0551.3970.0421.067
1-1/20.0721.8290.0601.5240.0491.245
20.0832.1080.0701.7780.0581.473
30.1092.7690.0902.2860.0721.829
40.1343.4040.1102.7940.0952.413

Source basis: exact conversion of CDA nominal inch dimensions (Tables 14.2a to 14.2c) using 25.4 mm per inch, rounded to three decimals.

<p>Copper Wall Thickness in Millimeters via <a href=”https://concretecalculate.com/copper-pipe-wall-thickness-chart/#wall-thickness-in-millimeters”>ConcreteCalculate.com</a></p>

ASTM B88 vs. B88M

Converting an inch-pound dimension does not create an interchangeable metric product designation. For metric-sized tube, use the matching ASTM B88M-26 requirements and confirm the product designation with the supplier.

Copper Pipe Wall Thickness Tolerances

Chart wall thickness values are nominal targets, not guaranteed minimums for every piece of tube, and ASTM B88 sets size-specific permitted variations. The applicable specification, size and measurement method control whether a tube is acceptable.

Nominal vs. Minimum Wall Thickness

A nominal wall of 0.045 inch does not mean every measurement will read 0.045 inch, and it is not a universal minimum. Pressure-rating calculations use a minimum wall value, which is a separate quantity from the nominal dimension.

Manufacturing Variation

Seamless drawn tube varies slightly in OD, wall and roundness along its length and around its circumference. Annealed and drawn tube also carry different OD tolerance values in the ASTM table.

Product Acceptance and Inspection

Formal acceptance uses the tolerances in the product standard, the required measurement procedure and the manufacturer’s documentation. A quick field reading is useful for identification but is not a substitute.

When to Consult the ASTM Specification

No Universal Tolerance Rule

This page does not give a single percentage tolerance or rejection threshold, because none applies to all copper products. Read Table 1 of the current ASTM B88 specification for the size and type in question.

How to Measure Copper Pipe Wall Thickness

To measure copper pipe wall thickness, cut the tube square, deburr the end, and measure across one wall at the open end with a tubing micrometer or a suitable caliper. Take several readings and compare their average with the nominal chart value.

Measuring a Cut Tube End

  1. Cut the tube square with a tube cutter or saw and remove the burr from the inside edge.
  2. Wipe the end clean so no chips or oxidation sit between the jaws.
  3. Confirm the nominal size first by measuring the OD, which should be about N + 0.125 inch.
  4. Measure the wall at four points around the end, roughly 90 degrees apart.

Using a Micrometer or Caliper

A tubing micrometer with a rounded anvil is made for this job. A flat-anvil micrometer or caliper jaw can sit on the curved bore and overstate the wall, so keep the jaws square across the wall and do not squeeze the tube.

Checking for Ovality or Deformation

Measure the OD in two directions at right angles. If the readings differ noticeably, the end is out of round and a wall reading there may mislead you. Cut back to a clean, round section and measure again.

Comparing Measurements With Nominal Values

Compare the average wall with the chart. A reading near 0.040 inch on a 0.625 inch OD tube points to 1/2 inch Type L, while 0.028 inch points to Type M. Treat this as identification only, since formal acceptance follows the ASTM specification.

Copper Pipe Color Codes and Identification

On drawn (hard) copper tube, the printed stripe is green for Type K, blue for Type L and red for Type M. Color helps sort stock, but incised markings and documentation are the reliable identifiers.

Copper Tube Color Codes (drawn tube)
Tube typePrinted colorGoverning standard
Type KGreenASTM B88
Type LBlueASTM B88
Type MRedASTM B88
ACRBlueASTM B280

Source: CDA commodity tube table and CDA Copper Tube and Pipe Standards.

Green: Type K

Green marks the thickest standard water tube, such as 0.049 inch wall at 1/2 inch.

Blue: Type L

Blue marks the intermediate wall, such as 0.040 inch at 1/2 inch. ACR tube also uses blue, so a blue stripe alone does not prove Type L.

Red: Type M

Red marks the thinnest water tube, such as 0.028 inch at 1/2 inch.

Permanent Tube Markings

CDA states that copper tube must be permanently marked (incised) to show tube type, the manufacturer’s name or trademark, and the country of origin. Hard tube also carries this information printed in a type-specific color. When marks are missing or worn, use measured OD and wall, supplier documents or a mill certificate.

Type K, L and M copper water tubes showing green, blue and red identification markings
Type K, L and M copper water tubes identified by their standard type markings.

Copper DWV Pipe Wall Thickness

Copper DWV tube is thinner than Type M at every size shown here, for example 0.042 inch against 0.058 inch at 2 inch nominal size. It is made under ASTM B306 for drain, waste and vent piping, not as a water-service tube.

ASTM B306 Drainage Tube

ASTM B306 covers copper drainage tube. ASTM’s catalog also lists a newer B306 edition, so verify the current edition before you cite it. DWV sizing follows the same nominal size plus 1/8 inch OD rule as water tube.

DWV vs. Type M

Copper DWV vs. Type M Wall Thickness (nominal, inches)
Nominal size (in.)DWV wall (in.)Type M wall (in.)
1-1/40.0400.042
1-1/20.0420.049
20.0420.058
30.0450.072
40.0580.095
60.0830.122

Source: CDA Copper Tube Handbook (A4015-24/23), Tables 14.2c and 14.2d.

<p>Copper DWV vs Type M Wall Thickness via <a href=”https://concretecalculate.com/copper-pipe-wall-thickness-chart/#copper-dwv-wall-thickness”>ConcreteCalculate.com</a></p>

Common DWV Thicknesses

DWV walls run from 0.040 inch at 1-1/4 inch to 0.083 inch at 6 inch in this table. Because it is a different product class, the DWV wall should not be used as a Type M value.

Why DWV Is Not a General Water-Pressure Substitute

CDA publishes calculated pressure ratings for DWV tube, but the product is intended for drainage service. Do not substitute it for water tube unless the design, specification and code allow it, and do not assume matching fittings or joint ratings.

ACR Copper Tubing Wall Thickness

ACR copper tubing follows ASTM B280 and is designated by its actual outside diameter, so a 1/2 inch ACR tube has a 0.500 inch OD. A 1/2 inch nominal Type L water tube has a 0.625 inch OD, so the two are not interchangeable.

ASTM B280 Refrigeration Tubing

ASTM B280 covers seamless copper tube for air-conditioning and refrigeration field service. CDA gives its dimensions in Table 14.2e and its rated working pressures in Table 14.3e.

Actual-OD Sizing

The size you buy is the OD you measure. A 1/2 inch ACR tube measures 0.500 inch, so its ID and wall are not found in the water-tube table.

Annealed vs. Drawn ACR Tube

For 1/2 inch OD, CDA’s table lists a 0.032 inch wall for annealed tube and a 0.035 inch wall for drawn tube. That temper-dependent wall is one reason ACR dimensions vary by product size and temper.

Copper water tube sizing versus ACR tube sizing Left: nominal 1/2 inch ASTM B88 Type L water tube with 0.625 inch actual outside diameter and 0.040 inch wall. Right: 1/2 inch outside diameter ASTM B280 ACR tube with 0.500 inch actual outside diameter and 0.035 inch drawn-temper wall. ASTM B88 water tube Sized by nominal size (Type L example) ASTM B280 ACR tube Sized by actual outside diameter Dashed ring: 0.625 in water tube OD for comparison Nominal size 1/2 in Actual OD 0.625 in Type L wall 0.040 in ID 0.545 in Designated size 1/2 in OD Actual OD 0.500 in Drawn-temper wall 0.035 in ID 0.430 in ACR example is a 1/2 in OD drawn-temper reference, not Type L water tube. ACR walls vary by size and temper. Schematic, drawn to one scale. Source: CDA Copper Tube Handbook, Tables 14.2b and 14.2e.
Difference between nominal-size copper water tubing and actual-outside-diameter ACR tubing.

Why ACR Dimensions Must Be Checked Separately

Use the ACR table for refrigeration tube and the Type K, L, M table for water tube. Mixing them leads to wrong IDs, wrong fittings and wrong flow checks. The example above is not Type L water tubing.

Copper Pipe Wall Thickness and Pressure Rating

Copper wall thickness helps set a tube’s calculated pressure rating, but it does not set the system’s allowable pressure on its own. Tube type, size, temper, temperature, fittings and joints all matter, and the lowest rating governs.

Thickness and Pressure Resistance

CDA’s calculated ratings follow the ASME B31 form shown below, where a thicker wall gives a higher result at the same stress.

P = 2 S tmin / (Dmax − 0.8 tmin)

Here P is allowable pressure (psi), S is the maximum allowable stress (psi), tmin is minimum wall (in.) and Dmax is maximum OD (in.). S changes with temper and temperature, so the nominal wall alone cannot give a rating.

Drawn vs. Annealed Temper

Drawn and annealed tube have different allowable stresses. When joints are brazed or welded, CDA says to use the annealed ratings, because heating anneals the tube near the joint.

Temperature Effects

CDA tabulates ratings for service temperatures from 100°F to 400°F, and the allowable value falls as temperature rises. Always read the row for your operating temperature.

Fittings and Joint Ratings

Tube, fitting and joint ratings must be considered together, and the lowest one governs the design pressure. In soldered systems the joint rating often governs, as shown in CDA Table 14.4a.

Why Pressure Ratings Are Not Universal

Where to Find Real Ratings

Use CDA Tables 14.3a to 14.3c for tube ratings by type, size, temper and temperature, and Table 14.4a for soldered and brazed joints. Our Pipe Pressure Rating Chart compares ratings across other pipe materials.

Copper Wall Thickness and Water Flow

Wall thickness affects water flow only through the inside diameter. At nominal 1/2 inch, the bore area is 0.218 in² for Type K, 0.233 in² for Type L and 0.254 in² for Type M.

Inside Diameter and Flow Area

Ai = π x ID² / 4

For 1/2 inch Type L: π x 0.545² / 4 = 0.233 in².

Comparing Type K/L/M Bore Areas

Nominal Bore Area at 1/2 Inch (A = pi x ID squared / 4)
TypeID (in.)Bore area (in²)
K0.5270.218
L0.5450.233
M0.5690.254

Source: calculated from CDA nominal dimensions; values agree with CDA’s calculated bore areas.

Type M gives about 16.5 percent more bore area than Type K at this size (0.254 / 0.218).

Why Flow Depends on the Complete System

Flow also depends on available pressure, tube length, fittings, elevation and velocity limits. CDA notes that above about 1-1/4 inch, the differences in bore area among Types K, L and M have virtually no effect on friction loss. For broader hydraulic analysis, see our Pipe Flow Rate Chart.

Copper Pipe Wall Thickness and Weight

Copper tube weight rises with wall thickness: nominal 3/4 inch tube weighs about 0.641 lb/ft in Type K, 0.455 lb/ft in Type L and 0.328 lb/ft in Type M. These are tube-only weights from nominal dimensions and copper density of 0.323 lb/in³.

Metal Cross-Sectional Area

Am = π/4 x (OD² − ID²) = π x t x (OD − t)

The area of copper in the wall is what carries the weight. A thicker wall means more copper per foot of tube.

Weight per Linear Foot

wft = 12 x Am x ρ (ρ = 0.323 lb/in³)

Type K vs. L vs. M Weight Comparison

Copper Tube Weight Comparison (tube only, lb per linear foot)
Nominal size (in.)Type K (lb/ft)Type L (lb/ft)Type M (lb/ft)
1/20.3440.2850.204
3/40.6410.4550.328
10.8390.6550.465
1-1/21.361.140.940
22.061.751.46
34.003.332.68

Source: CDA nominal-dimension calculated tube-only weights, Tables 14.2a to 14.2c. Excludes water, fittings, solder, insulation and packaging.

<p>Copper Tube Weight Comparison via <a href=”https://concretecalculate.com/copper-pipe-wall-thickness-chart/#wall-thickness-and-weight”>ConcreteCalculate.com</a></p>

Estimating Total Material Weight

Multiply the lb/ft value by the run length. For 20 feet of 3/4 inch Type L, 20 x 0.455 = 9.10 lb. For other materials, compare with the Pipe Weight Chart or run a quick estimate in the Pipe Weight Calculator.

Copper Pipe Wall Thickness and Joining Methods

Joining methods for copper tube depend on temper, size, fitting design and service, not on wall thickness alone. CDA notes that hard tube is usually soldered or brazed, while soft tube can also use flare and compression fittings.

Soldered Joints

Standard solder-joint pressure fittings are made for all K, L and M tube of a given nominal size because the OD is the same. CDA notes that in soldered systems, the joint rating often governs design pressure.

Brazed Joints

Brazing heat anneals tube near the joint, so CDA directs designers to use the annealed pressure ratings for brazed systems. A thin-wall tube has less metal to absorb that heat-affected zone, so apply the rating tables rather than assuming.

Press-Connect Fittings

Press-connect fittings are manufacturer-specific systems. Confirm that the fitting maker approves the tube type, size and temper you plan to use, and that its pressure and temperature rating covers the service.

Compression and Flared Connections

Flare and compression joints are typically used with soft (annealed) tube. They are not universal across all types or services, so follow the fitting manufacturer’s instructions and the code.

Copper Wall Thickness for Underground and Exposed Installations

Underground and exposed copper tube is chosen by service, code and conditions, not by one universal wall rule. CDA’s handbook recommends Type M hard for straight underground runs joined with fittings and Type L soft where coils are more convenient, subject to local code.

Buried Water Services

Buried service adds soil loading, possible damage during backfill and soil corrosivity. Some local codes or utilities require a heavier wall or a specific type for buried lines, so confirm before you order.

Aboveground Plumbing

Concealed or accessible interior runs more often use Type L or Type M. CDA’s guidance names Type M for water distribution above and below ground, with the local code deciding what is allowed.

Mechanical Damage and Corrosion Considerations

A thicker wall gives more material for impact, abrasion and long-term corrosion allowance, but it does not replace proper bedding, protection, sleeves and aggressive-soil evaluation.

Local Code and Project Requirements

Check Before You Specify

This section describes selection considerations, not a rule. The adopted plumbing code, the utility and the project specification control which type is acceptable for buried and exposed lines.

How to Calculate Copper Pipe Wall Thickness

The core calculation for copper tube is ID = OD − 2t, and every other quantity (bore area, weight, volume) follows from OD and wall. These are nominal dimensional and estimating calculations, not pressure ratings, code compliance or acceptance criteria.

Thickness From OD and ID

Formula 1: Wall Thickness From OD and ID

t = (OD − ID) / 2

Where: t = wall thickness (in.), OD = outside diameter (in.), ID = inside diameter (in.).

Example: 1/2 inch Type L: t = (0.625 − 0.545) / 2 = 0.040 in.

Result: 0.040 in. nominal wall.

Inside Diameter From Nominal Wall

Formula 2: Inside Diameter From Wall Thickness

ID = OD − 2t

Where: Same variables as Formula 1.

Example: 3/4 inch Type K: ID = 0.875 − 2(0.065) = 0.745 in.

Result: 0.745 in. nominal inside diameter.

Metal Cross-Sectional Area

Formula 4: Copper Metal Cross-Sectional Area

Am = π/4 x (OD² − ID²) = π x t x (OD − t)

Where: Am = copper area in the wall (in²).

Example: 3/4 inch Type L: π x 0.045 x (0.875 − 0.045) = 0.1173 in².

Result: About 0.1173 in² of copper.

Weight and Capacity Calculations

Formula 3: Internal Cross-Sectional Area

Ai = π x ID² / 4

Where: Ai = bore area (in²).

Example: 1/2 inch Type L: π x 0.545² / 4 = 0.2333 in². Bore areas at 1/2 inch: K 0.218, L 0.233, M 0.254 in².

Result: About 0.233 in² for Type L.

Formula 5: Approximate Copper Tube Weight

W = Am x L x ρ and wft = 12 x Am x ρ

Where: W = weight (lb), L = length (in.), ρ = 0.323 lb/in³, wft = lb per foot.

Example: 3/4 inch Type L: wft = 12 x 0.1173 x 0.323 = 0.455 lb/ft. For 20 ft: 20 x 0.455 = 9.10 lb.

Result: About 0.455 lb/ft, consistent with CDA. Excludes fittings, solder, insulation, water and packaging.

Formula 6: Percentage Difference in Wall Thickness

% difference = (tA − tB) / tB x 100

Where: tA and tB = the two walls being compared.

Example: 1/2 inch Type K vs. Type L: (0.049 − 0.040) / 0.040 x 100 = 22.5%.

Result: Type K is 22.5% thicker. This is a thickness comparison, not a pressure or service-life comparison.

Formula 7: Inches to Millimeters

t(mm) = 25.4 x t(in.)

Where: 25.4 mm = 1 in. (exact).

Example: 3/4 inch Type L: 0.045 x 25.4 = 1.143 mm.

Result: 1.143 mm.

Formula 8: Internal Water Volume

V(in³) = π x ID² / 4 x L and V(gal) = V(in³) / 231

Where: L = length (in.). One U.S. gallon = 231 in³.

Example: 10 ft (120 in.) of 3/4 inch Type L: V = π x 0.785² / 4 x 120 = 58.1 in³; 58.1 / 231 = 0.251 gal.

Result: About 0.251 U.S. gallon, consistent with CDA’s 0.0251 gal/ft. Assumes a straight, unobstructed tube at nominal dimensions.

Formula 4 Note

The shortcut Am = t(OD − t) must be multiplied by π. Without π the area is understated by a factor of about 3.14.

Copper Wall and Bore Lookup

Select a size and type to see nominal values calculated from the chart.

Calculated from nominal CDA dimensions with 0.323 lb/in³ copper density. Reference only, not an engineering design or acceptance tool.

Copper Pipe Wall Thickness vs. Steel Pipe Schedule

Copper uses Type K, L and M designations while steel pipe uses nominal pipe size (NPS) and schedule numbers, so Schedule 40 is not the same as Type L. At 1/2 inch, Type L has a 0.625 inch OD and 0.040 inch wall, while NPS 1/2 Schedule 40 steel has a 0.840 inch OD and 0.109 inch wall.

Copper Type Designations

Type K, L and M describe wall series within one OD family. The OD is fixed by the nominal size plus 0.125 inch, and only the wall changes.

Steel Pipe Schedule Designations

A schedule describes a wall series for a pipe size, and the OD of steel pipe is set by NPS. Use our Pipe Schedule Chart, Schedule 40 Pipe Chart and Schedule 80 Pipe Chart for steel dimensions.

Why Schedule 40 Is Not Type L

Copper Water Tube vs. Steel Pipe at the Same Trade Size (nominal, inches)
Trade size (in.)Copper Type L ODCopper Type L wallSteel pipe ODSteel Schedule 40 wall
1/20.6250.0400.8400.109
3/40.8750.0451.0500.113

Steel values: ASME B36.10M standard dimensions. Copper values: CDA Table 14.2b.

Avoiding Cross-Material Dimension Errors

Never copy an OD, ID or wall from one pipe system into another. For comparisons across materials, start from the Pipe Wall Thickness Chart, then return here for copper-specific thickness data.

How to Choose the Correct Copper Pipe Wall Thickness

Choose copper wall thickness by working through application, code, pressure and temperature, joining method and product specification, in that order. No single type is right for every job.

1. Identify the Application

Decide whether the tube carries potable water, hydronic heating water, refrigerant, fuel gas, drainage or medical gas, because each uses a different product family.

2. Check the Applicable Code

Read the adopted plumbing or mechanical code and the project specification. They decide which types are allowed, and ASTM B88 compliance alone does not approve an installation.

3. Confirm Pressure and Temperature

Use CDA Tables 14.3a to 14.3c at your operating temperature, using annealed ratings where brazing is used, and compare with fitting and joint ratings.

4. Check Joining Compatibility

Match the joining method, fitting manufacturer and tube temper. Then confirm the fitting approves the type and size.

5. Verify the Product Specification

Confirm ASTM B88 for water tube, ASTM B280 for ACR or ASTM B306 for DWV, and verify markings and mill documents on delivery.

Key Point

Copper pipe wall thickness cannot be selected from nominal size alone. The right reference depends on the product standard, type, service, operating conditions and installation requirements.

Common Copper Pipe Wall Thickness Mistakes

The most common copper wall thickness errors come from mixing tube families, treating nominal values as exact, and selecting by wall alone. Use this checklist before you order or accept tube.

Confusing Nominal Size With OD

Nominal 1/2 inch water tube has a 0.625 inch OD, not 0.500 inch.

Confusing ACR With Water Tubing

ACR is sized by actual OD under ASTM B280. 1/2 inch ACR is 0.500 inch OD.

Assuming Wall Thickness Sets Pressure Alone

Temper, temperature, fittings and joints also limit allowable pressure.

Ignoring Tolerances

Chart values are nominal. Check ASTM B88 Table 1 for permitted variation.

Using Incompatible Fittings

Check fitting approval for the tube type, size, temper and service.

Misreading Type Markings

Blue can mean Type L or ACR. Read the incised marking and documents.

Identification and Inspection Checklist

Copper Wall Thickness Identification Checklist
CheckWhat to verifyCommon mistake
Tube familyASTM B88, B280, B306 or another standardUsing the wrong dimensional chart
Nominal sizeMarked water-tube sizeAssuming nominal equals OD
Tube typeK, L, M, DWV or ACRUsing color alone
Outside diameterNominal dimensional referenceMeasuring a distorted section
Wall thicknessNominal value and applicable toleranceTreating chart value as exact measurement
TemperDrawn or annealedIgnoring joining and pressure implications
FittingApproved compatible fittingAssuming all copper fittings interchange
ServicePressure, temperature, fluidSelecting by thickness alone
ComplianceLocal code and specificationsAssuming national universal approval

Source: editorial checklist based on ASTM B88, B280 and B306 scope and the CDA Copper Tube Handbook (A4015-24/23).

<p>Copper Wall Thickness Identification Checklist via <a href=”https://concretecalculate.com/copper-pipe-wall-thickness-chart/#common-mistakes”>ConcreteCalculate.com</a></p>

Copper Pipe Wall Thickness FAQs

These answers cover the questions people ask most about copper tube walls. They use the nominal CDA values shown above.

What is the wall thickness of 1/2-inch copper pipe?

Nominal 1/2 inch ASTM B88 copper water tube has a 0.625 inch outside diameter. Its nominal wall is 0.049 inch for Type K, 0.040 inch for Type L and 0.028 inch for Type M, per CDA Tables 14.2a to 14.2c. These are nominal values, so actual tube varies within the ASTM B88 tolerances.

How thick is 3/4-inch Type L copper pipe?

Nominal 3/4 inch Type L copper tube has a 0.045 inch wall (1.143 mm) on a 0.875 inch outside diameter, which gives a nominal inside diameter of 0.785 inch. CDA lists its tube-only weight at 0.455 lb per foot. At the same size, Type K is 0.065 inch and Type M is 0.032 inch.

What is the wall thickness of 1-inch Type K copper?

Nominal 1 inch Type K copper tube has a 0.065 inch wall (1.651 mm) and a 1.125 inch outside diameter, so its nominal inside diameter is 0.995 inch. At the same size, Type L is 0.050 inch and Type M is 0.035 inch, according to CDA’s nominal dimension tables.

Which is thicker, Type K or Type L?

Type K is thicker than Type L at every nominal size where both are listed. At 1/2 inch, K is 0.049 inch and L is 0.040 inch, so K is 22.5 percent thicker. Both share the same outside diameter, so Type K has the smaller inside diameter. Thickness alone does not decide which type a project requires.

Is Type M thinner than Type L?

Yes. At any nominal size, Type M has a thinner wall than Type L, for example 0.028 inch versus 0.040 inch at 1/2 inch and 0.032 inch versus 0.045 inch at 3/4 inch. CDA lists Type M only in drawn temper. Whether it is allowed for a given potable water installation depends on the local plumbing code.

What is the actual OD of 1/2-inch copper pipe?

Nominal 1/2 inch copper water tube (Types K, L and M) has an actual outside diameter of 0.625 inch, because ASTM B88 sizing adds 0.125 inch to the nominal size. A 1/2 inch ACR refrigeration tube is a different product, with a 0.500 inch actual outside diameter.

Is copper pipe measured by ID or OD?

Copper water tube is named by nominal size, not by a direct measurement. Its actual OD is always the nominal size plus 0.125 inch, and the inside diameter depends on tube type and wall thickness. ACR refrigeration tubing is the exception, because it is designated by its actual outside diameter.

How do you calculate copper pipe inside diameter?

Subtract twice the wall thickness from the outside diameter: ID = OD − 2t. For 3/4 inch Type L, 0.875 − 2(0.045) = 0.785 inch. Use nominal wall values for planning, because a measured inside diameter varies slightly with tube tolerances and any out-of-round condition.

How do you measure copper wall thickness?

Cut the tube square, deburr the end, and measure across the wall at the open end with a tubing micrometer or a suitable caliper. Take readings at about four points around the circumference and average them. Compare the average with the nominal chart value, but remember that formal acceptance follows ASTM tolerances.

Does Type K have a higher pressure rating than Type L?

Not as a simple rule. Rated working pressure depends on tube type, size, temper, temperature and joining method, and the lowest rating among tube, fitting and joint governs. A thicker wall usually raises the calculated tube rating, but a soldered joint often limits the system. Check CDA Tables 14.3a to 14.4a.

Can Type M be used for potable water?

Often yes, but it depends on the code adopted where you build. ASTM B88 covers Type M as a water tube and CDA lists domestic water service and distribution among its applications, yet some jurisdictions restrict certain uses, such as buried service. Confirm with the local plumbing code and the project specification.

What is the difference between copper DWV and Type M?

DWV tube follows ASTM B306 and is made for drain, waste and vent piping, while Type M follows ASTM B88 for water service. DWV is thinner than Type M at every size in the comparison table, for example 0.042 inch versus 0.058 inch at 2 inch. They are separate products and should not be swapped.

Is ACR copper the same as Type L?

No. ACR tube follows ASTM B280 and is designated by actual outside diameter, so 1/2 inch ACR measures 0.500 inch. Nominal 1/2 inch Type L water tube follows ASTM B88 and measures 0.625 inch. Both can carry blue identification, so check the incised marking and size rather than relying on color.

Does copper pipe have Schedule 40 or Schedule 80?

No. Standard copper water tube is classified as Type K, L or M, and ACR and DWV have their own designations. Schedule 40 and Schedule 80 are wall series for steel and plastic pipe, which use different outside diameters. Schedule 40 is not equivalent to Type L, so never transfer dimensions between the systems.

What is the difference between ASTM B88 and B88M?

ASTM B88 is the inch-pound specification for seamless copper water tube, listed by ASTM as B88-22. B88M is the SI companion, listed as B88M-26. A converted inch dimension is not automatically a B88M product designation, so use the matching standard and confirm designations with the supplier.

What do green, blue and red copper markings mean?

On drawn (hard) tube, the printed color stripe identifies the type: green for Type K, blue for Type L and red for Type M. The stripe also carries the manufacturer and country of origin. ACR tube also uses blue, so rely on the incised markings and documentation, not color alone.

How much does copper pipe weigh per foot?

Tube-only weight depends on type and size. At 1/2 inch, CDA lists 0.344 lb/ft for Type K, 0.285 lb/ft for Type L and 0.204 lb/ft for Type M. At 3/4 inch the values are 0.641, 0.455 and 0.328 lb/ft. These exclude water, fittings, solder and insulation.

Can different copper tube types use the same fittings?

Types K, L and M of the same nominal size share one outside diameter, so standard solder-joint fittings for that size generally fit all three. Mechanical and press fittings, however, must be approved by the manufacturer for the tube type, size and temper, and ACR sizing is different. Check fitting ratings and local code.

Does copper wall thickness affect water flow?

Yes, through the inside diameter. At 1/2 inch, nominal bore area is 0.218 in² for Type K, 0.233 in² for Type L and 0.254 in² for Type M. Actual flow also depends on pressure, length, fittings and velocity limits, and above about 1-1/4 inch CDA says the type has virtually no effect on friction loss.

Can Type L be substituted for Type K?

Only if the project specification, plumbing code and engineer allow it. Types K and L share the same outside diameter, so fittings fit, but Type L has a thinner wall, a larger bore and a lower calculated pressure rating at the same temper. Verify rating, service conditions and approval before substituting.

Key Takeaway

This copper pipe wall thickness chart gives nominal Type K, L and M walls, inside diameters, millimeter values and tube weights for ASTM B88 water tube, with separate DWV and ACR references. Use it to identify and compare tube, then confirm tolerances, pressure ratings, fittings and code approval before you buy or install. For broader sizing, see our Copper Pipe Size Chart, and for materials other than copper, use the Pipe Wall Thickness Chart.

Download Copper Wall Thickness Chart PDF

Use your browser’s print function to save this page as a print-ready PDF for jobsite binders, estimating folders and shop reference. Interactive tools and placeholders are hidden in the printed version.

Type K, L and M wall thickness chartInside diameter and millimeter tablesDWV and ACR comparisonTube weight per foot tableFormulas and worked examplesIdentification checklist

Cite or Embed This Chart

Copy the code below to cite the full copper pipe wall thickness chart on your own page. Each section above also has its own Copy Citation button, and each table has an Embed This Table button.

<p>Source: <a href=”https://concretecalculate.com/copper-pipe-wall-thickness-chart/”>Copper Pipe Wall Thickness Chart, ConcreteCalculate.com</a></p>

Sources and References

Dimensions are nominal values for reference. Confirm current ASTM editions, local code adoption and manufacturer approvals before specifying or installing.