Beam Load Calculator 2026 Simply Supported, Cantilever & Fixed Beams
Find the maximum safe load, shear force, bending moment, and deflection for steel, wood, and concrete beams. Results include automatic IBC 2024 Table 1604.3 deflection checks and AISC 360-22 allowable stress verification.
How This Beam Load Calculator Works
Choose Support Condition
Select simply supported, cantilever, or fixed-fixed. Each produces a different bending moment formula and reaction distribution.
Define Load and Span
Enter the applied load and clear span. Select point load at center, at any position, or a uniform distributed load in lb/ft.
Pick Material and Section
Choose from steel A36/A992 presets, lumber species, or enter custom Fb and E. Use the W-shape or lumber section database.
Get Capacity and Code Check
Results show maximum safe load, actual vs. allowable bending stress, shear force, reaction forces, and IBC 2024 deflection pass/fail.
Allowable Bending Stress Reference by Material
Allowable bending stress (Fb) is the primary input governing safe load capacity. The table below lists values per AISC 360-22 and NDS 2018. For deflection limits that apply to this calculator, the beam deflection calculator covers all IBC Table 1604.3 scenarios in depth.
| Material | Grade / Spec | Fy or Fb (psi) | ASD Fb (psi) | E (psi) | Standard |
|---|---|---|---|---|---|
| Structural Steel | ASTM A36 | 36,000 | 23,760 | 29,000,000 | AISC 360-22 Chapter F |
| Structural Steel | ASTM A992 | 50,000 | 33,000 | 29,000,000 | AISC 360-22 Chapter F |
| Douglas Fir-Larch | No. 2, 2-3" thick | 875 | 875 | 1,600,000 | NDS 2018 Supp. Table 4A |
| Southern Pine | No. 2, 2-3" thick | 1,000 | 1,000 | 1,400,000 | NDS 2018 Supp. Table 4B |
| Hem-Fir | No. 2, 2-3" thick | 850 | 850 | 1,300,000 | NDS 2018 Supp. Table 4A |
| Glulam | 24F-V4 (Douglas Fir) | 2,400 | 2,400 | 1,800,000 | NDS 2018 Supp. Table 5A |
| LVL | 1.9E Grade | 2,600 | 2,600 | 1,900,000 | NDS 2018 Supp. Table N1 |
Source: AISC Steel Construction Manual, 16th Ed. Table 1-1; NDS 2018 Supplement Tables 4A-4B. ASD Fb for compact steel = 0.66 × Fy, assuming full lateral bracing per AISC 360-22 Section F2.
Bending Moment and Shear Formulas Used
This calculator uses the standard structural beam formulas from AISC Steel Construction Manual Table 3-22 and Roark's Formulas for Stress and Strain, 8th Edition. For combined bending and axial load scenarios, refer to the concrete stress calculator.
Mmax = PL / 4
Vmax = P / 2
Pallow = 4 × Fb × S / L
AISC Table 3-22a, Case 1
Mmax = wL² / 8
Vmax = wL / 2
wallow = 8 × Fb × S / L²
AISC Table 3-22a, Case 2
Mmax = PL
Vmax = P
Pallow = Fb × S / L
Roark's 8th Ed., Table 8.1
Mmax = wL² / 2
Vmax = wL
wallow = 2 × Fb × S / L²
Roark's 8th Ed., Table 8.1
Mmax = PL / 8
Vmax = P / 2
Pallow = 8 × Fb × S / L
Roark's 8th Ed., Table 8.2
Mmax = wL² / 12
Vmax = wL / 2
wallow = 12 × Fb × S / L²
Roark's 8th Ed., Table 8.2
Where: Mmax = maximum bending moment (lb-in), P = point load (lb), w = distributed load (lb/in), L = span (in), Fb = allowable bending stress (psi), S = section modulus (in³), V = maximum shear force (lb).
Understanding Beam Load Capacity
Beam load capacity is the maximum load a beam can carry before the internal bending stress exceeds the material's allowable limit. It is controlled by three variables: span length, section modulus, and allowable bending stress. Doubling the span cuts the point load capacity in half, while doubling the section depth increases capacity by roughly four times because section modulus scales with the square of depth.
Two separate limits must be satisfied. The strength limit checks that the actual bending stress (M/S) does not exceed Fb from AISC 360-22 or NDS 2018. The serviceability limit checks that deflection does not exceed L/360, L/240, or L/480 per IBC 2024 Table 1604.3. A beam can pass the strength check and still fail the deflection check, particularly on long spans. For combined loading scenarios, the concrete load-bearing capacity calculator covers axial plus bending interaction.
Maximum shear force controls design at support points and governs for short, heavily loaded beams. For simply supported beams under UDL, maximum shear equals wL/2 and occurs directly at each support. For steel beams, allowable shear stress is 0.4 × Fy per AISC 360-22 Section G2.1. For wood, allowable horizontal shear stress (Fv) from NDS 2018 ranges from 135 psi for Douglas Fir to 175 psi for Southern Pine.
Span-to-Depth Ratio Guidelines
| Beam Type | Material | Span/Depth Ratio | Source |
|---|---|---|---|
| Simply Supported Floor Beam | Steel | 20–24 | AISC Design Guide 3 |
| Simply Supported Floor Beam | Wood | 12–18 | NDS Commentary 2018 |
| Cantilever | Steel | 8–12 | AISC Design Guide 3 |
| Roof Beam (light) | Steel | 24–30 | AISC Design Guide 3 |
| Glulam Roof Beam | Glulam | 14–20 | APA EWS Data File E20W |
Sample Load Capacity Calculations
These worked examples follow AISC 360-22 and NDS 2018 formulas. For rebar sizing in the supporting concrete structure, the rebar spacing calculator handles that step separately.
Example 1 — Steel Floor Beam, Simply Supported
| Span | 18 ft (216 in) |
| Section | W12x35 (Sx = 46.8 in³) |
| Material | A36 Steel (Fb = 23,760 psi) |
| Load Type | UDL |
| Application | Floor Live Load (L/360) |
Calculation: w = 8 × 23,760 × 46.8 / 216² = 189.7 lb/in = 2,275 lb/ft. Deflection check: I = 285 in⁴; δallow = 216/360 = 0.600 in; governs at ~1,600 lb/ft for a deflection-controlled result.
Example 2 — Wood Cantilever Beam
| Span | 6 ft (72 in) |
| Section | 4x12 Lumber (S = 73.8 in³) |
| Material | Douglas Fir No. 2 (Fb = 875 psi) |
| Load Type | Point Load at Free End |
| Application | Cantilever L/180 |
Calculation: P = Fb × S / L = 875 × 73.8 / 72 = 895 lb. Deflection: δ = PL³/(3EI) = 895 × 72³ / (3 × 1,700,000 × 415) = 0.298 in; L/180 = 0.400 in. PASS.
Example 3 — Steel A992 Fixed-Fixed Beam
| Span | 24 ft (288 in) |
| Section | W16x36 (Sx = 56.5 in³) |
| Material | A992 Steel (Fb = 33,000 psi) |
| Load Type | UDL |
| Application | Floor Total Load (L/240) |
Calculation: w = 12 × 33,000 × 56.5 / 288² = 270.1 lb/in = 3,241 lb/ft. Deflection check I = 448 in⁴; δallow = 288/240 = 1.200 in governs at 2,700 lb/ft. PASS at 2,700 lb/ft.
Common Beam Load Calculation Mistakes
A cantilever with a point load at the free end has M = PL, while a simply supported beam under the same load has M = PL/4. Using the wrong formula overstates capacity by a factor of 4 for cantilevers. Per AISC Steel Construction Manual Table 3-22, each support condition and load pattern produces a distinct moment coefficient.
Section modulus S = I/c controls bending strength: Mallow = Fb × S. Moment of inertia I controls deflection: δ = PL³/(48EI). Using I in place of S in the bending formula overstates capacity dramatically. For a W12x35, S = 46.8 in³ but I = 285 in⁴, a factor of 6 difference.
The bending moment formula M = PL/4 requires L in inches when P is in pounds and Fb is in psi. Using L = 20 ft instead of 240 in understates the moment by a factor of 12 and falsely overstates the safe load. This calculator handles unit conversion automatically.
Many calculations stop after the bending stress check. Per IBC 2024 Table 1604.3, deflection governs most real-world floor beams. A W14x22 over 20 ft will pass the bending stress check at 2,000 lb total UDL but deflect 0.82 in under that load, exceeding the L/360 limit of 0.667 in. Deflection, not stress, is the binding constraint on long-span beams.
AISC 360-22 Section F2 allows Fb = 0.66Fy only when the compression flange is fully braced against lateral-torsional buckling. If the beam has no mid-span bracing, the allowable stress must be reduced using the lateral-torsional buckling provisions in AISC 360-22 Section F2.2. Unbraced compact beams can see Fb reductions of 30 to 50 percent on spans over 15 feet.
Sizing tip: For steel floor beams, target a span-to-depth ratio of 20-24. A 20-foot beam wants a depth of approximately 10-12 inches, pointing to a W10 or W12 series. This rule often produces a deflection-controlled design that passes both the strength and serviceability checks simultaneously. See AISC Design Guide 3 for full guidance on serviceability-controlled steel beam design.
IBC 2024 Deflection Limits — Quick Reference
Both the strength check and the deflection check must pass independently. The slab load calculator applies the same L/360 and L/240 limits for two-way concrete slabs.
| Element | Load Case | Limit | 20 ft Span Example |
|---|---|---|---|
| Floor beams | Live load (L) | L/360 | 0.667 in |
| Floor beams | Total load (D+L) | L/240 | 1.000 in |
| Roof beams | Live load (L) | L/360 | 0.667 in |
| Roof beams | Total load (D+L) | L/240 | 1.000 in |
| Brittle finishes (tile, plaster) | Live load (L) | L/480 | 0.500 in |
| Cantilevers | Live load (L) | L/180 | 1.333 in (10 ft cant.) |
Source: IBC 2024 Table 1604.3. L is the clear span in inches. For steel members, dead-load deflection may be set to zero per Table 1604.3 footnote (g).
Frequently Asked Questions
For a simply supported W12x35 (Sx = 46.8 in³) in A36 steel (Fb = 23,760 psi) under UDL over a 20-foot span: wallow = 8 × 23,760 × 46.8 / 240² = 154.9 lb/in = 1,859 lb/ft for bending strength alone. The deflection check using I = 285 in⁴ reduces this to roughly 1,400 lb/ft for the L/360 floor limit. Use this calculator to confirm both checks simultaneously.
A fixed-fixed beam carries 2 to 3 times more load than a simply supported beam of the same span and section. Under a center point load, the bending moment coefficient changes from PL/4 to PL/8, meaning the same beam can carry twice the point load at the same stress. Under UDL, the coefficient changes from wL²/8 to wL²/12, a 50% increase in capacity. Deflection also decreases 4x. These advantages require the end connections to be designed as moment connections, which adds fabrication cost.
This calculator applies to non-composite beams, where the steel section alone resists all bending. For composite beams (steel beam acting together with a concrete slab via shear studs), the effective section modulus is higher and must be calculated using the transformed section method per AISC 360-22 Chapter I. Composite floor beams can achieve 30 to 50 percent more capacity than the steel section alone. For the concrete component, refer to the concrete flexural strength calculator.
Per AISC 360-22 Section G2.1, nominal shear capacity is Vn = 0.6 × Fy × Aw × Cv1, where Aw = d × tw (web area) and Cv1 = 1.0 for most standard W-shapes with h/tw ≤ 2.24√(E/Fy). For A36 steel, h/tw must not exceed 53.9 for Cv1 = 1.0. For ASD, allowable shear Va = Vn / Ωv = Vn / 1.67. A W12x35 with Aw = 12.5 × 0.30 = 3.75 in² has Va = 0.6 × 36,000 × 3.75 / 1.67 = 48,500 lb, which rarely governs on spans over 10 feet under normal floor loads.
Allowable Stress Design (ASD) limits the actual bending stress (M/S) to an allowable value (Fb = 0.66Fy for compact sections with full bracing). Load and Resistance Factor Design (LRFD) amplifies loads using factors (1.2D + 1.6L) and checks the beam against its full nominal capacity reduced by a resistance factor (φb = 0.90). Both are permitted under AISC 360-22. ASD is common for simple projects because it uses unfactored service loads directly. LRFD is more efficient on complex projects where dead and live loads differ significantly. For equivalent spans and loads, ASD typically gives a slightly more conservative result than LRFD by about 10 to 15 percent.
Steel has a significantly higher strength-to-weight ratio. An A36 W12x35 weighing 35 lb/ft can carry roughly 25 to 30 times the bending moment of a 2x12 Douglas Fir board at 3 lb/ft. However, wood is more practical for residential spans under 20 feet because it is easier to cut, fasten, and frame on site. For long residential spans (over 16 feet), LVL and glulam bridge the gap, with Fb values of 2,400 to 2,600 psi versus 875 psi for dimension lumber. The concrete beam calculator covers reinforced concrete beam options.
Yes. Self-weight acts as an additional UDL that consumes part of the beam's bending capacity. A W14x48 beam weighing 48 lb/ft over a 24-foot span generates a self-weight moment of 48 × 288² / 8 = 497,664 lb-in, which must be subtracted from the total allowable moment before calculating safe applied load. For steel beams, self-weight typically consumes 5 to 15 percent of total capacity on spans under 30 feet. Use the self-weight field in Advanced Options to include this in the calculation.
Sources and Methodology
- AISC Steel Construction Manual, 16th Edition (2022) — Table 1-1 W-shape section properties, Table 3-22 beam diagrams and formulas, Chapter F allowable bending stress. aisc.org/manual
- AISC 360-22 Specification for Structural Steel Buildings — Section F2 flexural capacity of compact sections; Section G2.1 shear capacity. aisc.org/360-22
- IBC 2024 International Building Code — Table 1604.3 allowable deflections for structural members. iccsafe.org
- NDS 2018 National Design Specification for Wood Construction — Supplement Tables 4A-4B reference design values for sawn lumber; Table 5A for glulam. awc.org
- Roark's Formulas for Stress and Strain, 8th Edition (2012) — Table 8.1 cantilever beams; Table 8.2 fixed-fixed beams. Warren Young, Richard Budynas, Ali Sadegh.
- APA EWS Data File E20W — Span-to-depth ratios and design values for structural glulam beams. apawood.org
Last reviewed May 2026. Built by Muhammad Ramzan Babar, physics researcher (PhD candidate). Reviewed by site author.
⚠ Engineering Disclaimer
This calculator provides estimates for planning purposes. For permitted structural work, foundations, multi-story construction, retaining walls over 4 feet, and commercial projects, calculations must be verified by a licensed structural engineer per IBC 2024 Section 1604. ConcreteCalculate.com is not liable for structural decisions made from these estimates.
Allowable bending stress values assume compact sections with full lateral bracing of the compression flange per AISC 360-22 Section F2. Unbraced beams require lateral-torsional buckling checks that reduce allowable stress. Wood beam values assume dry service conditions, normal load duration, and no size factor adjustments per NDS 2018 Section 4.3.
🔒 Privacy
All calculations run locally in your browser. No measurements, project details, or results are sent to any server. No account or signup is required to use this calculator.
Save & Download Your Concrete Results
Your calculation is ready. Enter your email to unlock:
- ✔ Download a printable PDF estimate
- ✔ Get 2026 US concrete material prices
- ✔ Save your project calculations instantly
- ✔ Access contractor cost-saving tips